Ghaddar Generator DT30 – DT33S (1500 rpm) powered by John Deere

Product description

Ratings @ 0.8 PF

Voltage*

230/400 V

Frequency*

50 Hz

Prime rating

DT30*

30 KVA

Stand-by Rating

DT33S*

33 KVA

Ghaddar Generator DT30 – DT33S (1500 rpm) powered by John Deere

Notes

  1. The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
  2. This generating set is of fixed speed of 1500 rpm.
  3. DT30 (prime power): variable load and unlimited hour usage with an average load factor of 80% of the prime rating over each 24-hour period. A 10% overload is permitted for 1 hour in every 12 hours of operation.
  4. DT33S (standby power): variable load limited to an annual usage up to 500 hours, of which 300 hours may be continuous running. No overload is permitted.

Engine Technical Data

Make & Model / GSPUJOHN DEERE 3029DFG20 / 3029DFU20
Cylinders & Arrangement3; vertical in-line
Bore & Stroke (mm)106 × 110 mm
Induction systemTurbocharged & aftercooled
CombustionDirect injection
Cycle4 stroke
Compression ratio17.2:1
Cooling SystemWater cooled
Displacement2.9 liters
Lube oil capacity6 liters Max
Coolant capacity13 liters
Standard governor (Optional)Mechanical (Electronic)
Engine Speed1500 rpm
Fuel & Oil ConsumptionFuel Cons.Oil Cons.
Consumption @ 100% Load (L/H)7.40.019
Consumption @ 75% Load (L/H)5.50.010
Consumption @ 50% Load (L/H)3.90.014
Consumption @ 25% Load (L/H)2.40.006
Radiator Cooling Air Flow (m3/s)2.0
Emissions regulationsFor non-regulated territories
Exhaust temperature (°C, max)610
Max exhaust gas flow (m3/min)5.2
Max. allowed back pressure (kPa)7.5

The above performance data are valid as per the following specs:

  • Diesel fuel according to EN590 standard or equivalent.
  • Lubricating oil according to Grade SAE 15W-40 API CI4 or CJ4.
  • Antifreeze compliant with ASTM D6210.

Alternator Technical Data

Make & ModelLeroy Somer TAL042C
Frequency / No. of poles50Hz / 4P
Ingress protectionIP23
Insulation classH
Terminals (Optional)6 (12)
Excitation systemSHUNT
Winding pitch2/3
AVR modelR120
Overspeed2250 R.P.M.
Voltage regulation± 1 %
Coolant air flow0.1 m3/s

Certification

  • The complete generating set is type-tested according to ISO 8528-8.

Control Panel Specifications

Control Panel

GMP260MKIII (DSE6110 MKIII) panel is an automatic start generating-set panel of microprocessor-based design which interfaces with electronic engines via CAN-bus J1939. It is fully configurable by PC software, and most settings can be programmed via front fascia buttons. If mains voltage is to be monitored, DSE6120MKIII can be offered. Circuit Breaker Schneider or ABB, 3-Pole MCB (4-Pole optional).

Construction

Sheet FabricationCNC shearing & bending
Paint typeHeat-treated powder-coated
Paint applicationElectrostatic corona spraying
Durability tests
  • Impact [EN ISO 6272]
  • Salt spray resistance [ASTM B117-73]
  • Humidity resistance [ASTM D2247]
Compliance
  • Panel compliant with [ISO 8528-8]
  • Clearance & Creepage [IEC60355-1]
  • Leakage current & Dielectric strength [IEC60355-1]
  • Protection against electric shock [IEC600 364-4-41]
Degree of protectionIP55
Wire crimping
  • Crimping force up to 20 kN
  • Accuracy of 0.01 mm
  • Each crimp checked by Komax CFA+
Wire coding
  • Wires coded by color and cross-section
  • Wires coded by printed numbers
  • Wires coded by printed function

Control Panel Protections, Control & Instrumentation

Protection (standard)(OPTIONAL Note 1,3)Control (standard)(OPTIONAL Note 1)Instrumentation (standard)(OPTIONAL Note 1,3)
Over / Under AC VoltageHigh Oil TemperatureRemote Start InputBattery Charger: 5A, 10A, ULGen AC Voltage: 3ph VLL & VLNLube Oil Temperature
Over / Under FrequencyHigh Exhaust TemperatureEmergency Stop ButtonFuel Pump ControlGen Frequency: HzExhaust Temperature
Delayed Over CurrentLow Fuel PressureCommon Alarm Volt-Free ContactExtension:Gen Current: 3 phase AEngine inlet air (Boost) pressure
Short-circuitLow Coolant PressureEvent Log (100 Events)Ethernet – Modbus TCPPower: kW, kVA, kVAr & PFCharging Ammeter
Over kWLow Fuel LevelWeekly ExerciserRS485 – Modbus RTUEnergy: kW·h, kVA·h, kVAr·hFuel Pressure
High Engine TemperatureLow Oil LevelAudible AlarmGPS TrackerLube Oil PressureCoolant Pressure
Low Oil PressureHigh Winding TemperatureStandard CANbus J1939Water in Fuel DetectionEngine Coolant TemperatureFuel Level
Maintenance AlarmHigh Bearing TemperaturePre/Post Heat ControlWebnet ApplicationsBattery DC VoltageLube Oil Level
High / Low Battery VoltageLow Boost PressureData LoggingSNMP GatewayDC AlternatorWinding temperature 3×RTD
Low Coolant Level (Note 2)Fusible Link Fire ProtectionPLC EditorInputs: 20 mA, 10 VEngine SpeedBearing Temperature RTD
3 ph Mains Sensing (6120)Low Coolant TemperatureOil Level ControlThermocouplesOperating HoursTier 4 Support

Note 1: Some OPTIONAL features could be standard if CANbus is established within electronic engines.

Note 2: Low coolant level protection is standard for gensets above 200 kVA; otherwise it is optional.

Note 3: There is a limitation in the number of protections and measurements that can be offered with GMP260MK. Other control panels & modules can be offered as required (DSE 7310/20, 7410/20, 8610, 8810, and others).

Genset Standard Features

Assembly: Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528.

Fabrication:

  • Engine/alternator assembly rests on skid with anti-vibration mounting pads
  • Skid made of durable sheet metals and beams exceeding vibration & torsion norms
  • Skid-mounted fuel tank with fuel gauge, filler cap, fuel inlet and outlet hoses
  • Control panel enclosure made of reliable metal sheet

Paint:

  • Heat-treated, powder-coated electrostatic corona spraying
  • Durability tests conforming to international standards:
    • Impact (EN ISO 6272)
    • Salt Spray Resistance (ASTM B117-73)
    • Humidity Resistance (ASTM D2247)

Works-Testing:

  • All gensets tested prior to dispatch
  • Automatic test generated and checked according to ISO 8528
  • Test certificate issued for each genset

Equipment:

  • Water-cooled radiator with belt-driven blower fan and full guarding
  • Electric starter with solenoid relay
  • Battery charging alternator
  • Energized-to-run solenoid
  • Replaceable fuel, oil and air filters
  • Heavy-duty lead-acid battery with matching capacity (Amps & CCA)
  • Industrial exhaust silencer – 16 dB noise reduction
  • Integral fuel tank with 100 L capacity

Documentation:

  • User Manual for operation, installation and maintenance
  • Wiring diagram
  • Test report
  • Maintenance schedule
  • Catalogues for Engine, Alternator & AVR

Genset Optional Features

  • Manual & Automatic Transfer Switches
  • Synchronizing & Totalizing Panels
  • Fuel water separator
  • Water jacket heater
  • Oil heater
  • Fuel heater
  • Battery heater
  • Anti-condensation heater
  • Air shut-off valve
  • Oil sampler
  • Pre-lube oil pump

Shipping Dimensions (Open Set):

  • Length: 1700 mm
  • Width: 770 mm
  • Height: 1220 mm
  • Weight: 553 Kg