Product description
Ratings @ 0.8 PF
Voltage*
220/380 V
127/220 V
277/480 V
Frequency*
60 Hz
60 Hz
60 Hz
Prime rating
PT24*
23.9 KVA
23.9 KVA
23.9 KVA
Stand-by Rating
PT27S*
26.5 A
26.5 A
26.5 A
Ghaddar Generator KT24 – KT27S (1800 rpm) powered by Kubota
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
Notes
- The applicable voltage range is 220V, 380V to 480V for 60Hz applications. For other voltages, please consult factory.
- This generating set is of fixed speed of 1800 rpm.
- KT24 (prime power): variable load, unlimited hours, average load factor 80% per 24h. 10% overload permitted for 1 hour in every 12h.
- KT27S (standby): variable load limited to 500h annually (300h continuous). No overload permitted.
Engine Technical Data
| Make & Model | KUBOTA V2203-E2-BG-GDR1 |
|---|---|
| Cylinders & Arrangement | 4; vertical in-line |
| Bore & Stroke (mm) | 87 × 92.4 |
| Induction system | Naturally aspirated |
| Combustion | Indirect injection |
| Cycle | 4 stroke |
| Compression ratio | 22 |
| Cooling System | Water cooled |
| Displacement | 2.197 liters |
| Lube oil capacity | 7.6 liters Max |
| Coolant capacity | 8.1 liters |
| Standard governor | Isochronous Electronic |
| Engine Speed | 1800 rpm |
| Fuel Consumption @ 100% Load | 5.2 (L/H) |
| Fuel Consumption @ 75% Load | 3.9 (L/H) |
| Fuel Consumption @ 50% Load | 2.6 (L/H) |
| Fuel Consumption @ 25% Load | 1.3 (L/H) |
| Radiator Cooling Air Flow | 0.80 m3/s |
| Emissions regulations | EU Stage IIIA |
| Exhaust temperature (max) | 500 °C |
| Max exhaust gas flow | 5.17 m3/min |
| Max. allowed back pressure | 7.1 kPa |
The above performance data are valid as per the following specs:
- Diesel Fuel according to BS2869 Class A2 or equivalent.
- Lubricating oil according to Grade SAE 15W-40 API CI4.
- Coolant: 50% antifreeze and 50% fresh water.
Alternator Technical Data
| Make & Model | Leroy Somer TAL042A |
|---|---|
| Frequency / No. of poles | 60Hz / 4P |
| Ingress protection | IP23 |
| Insulation class | H |
| Terminals (Optional) | 6 (12) |
| Excitation system | SHUNT |
| Winding pitch | 2/3 |
| AVR model | R120 |
| Overspeed | 2250 R.P.M. |
| Voltage regulation | ± 1 % |
| Alternator air flow | 0.07 m3/s |
Certification
- The complete generating set is type-tested according to ISO 8528-8 standard.
Control Panel Specifications
GMP260MK (DSE6110 MKII) panel is an automatic start generating-set panel of microprocessor-based design, capable of interfacing with electronic engines through CAN-bus J1939. Fully configurable by front fascia buttons and PC software. If mains voltage is to be monitored, DSE6120MKII can be offered. Circuit breaker Schneider or ABB, 3-Pole MCB (4-Pole optional).
Construction
| Sheet Fabrication | CNC shearing & bending |
|---|---|
| Paint type | Heat-treated powder-coated |
| Paint application | Electrostatic corona spraying |
| Durability tests |
|
| Compliance |
|
| Degree of protection | IP55 |
| Wire crimping |
|
| Wire coding |
|
Certification
- The control panel is certified by an ISO17025 accredited laboratory to have IP55 according to IEC60355.
Genset Standard Features
Assembly: Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528.
Fabrication:
- Engine/alternator assembly rests on skid with anti-vibration mounting pads.
- Skid made of durable sheet metals and beams exceeding vibration & torsion resistance norms.
- Skid-mounted fuel tank supplied with gauge, filler cap, fuel inlet & outlet hoses.
- Control panel enclosure made of reliable metal sheet.
Paint:
- Heat-treated, powder-coated electrostatic corona spraying.
- Durability tests: Impact (EN ISO 6272), Salt Spray (ASTM B117-73), Humidity (ASTM D2247).
Works-Testing:
- All gensets tested prior to dispatch.
- Test auto-generated and checked according to ISO8528.
- Test certificate issued for each genset.
Equipment:
- Water-cooled radiator with belt-driven blower fan and full guarding
- Electric starter with solenoid relay
- Battery charging alternator
- Energized-to-run solenoid
- Replaceable fuel, oil and air filters
- Heavy-duty lead-acid battery with matching capacity (Amps & CCA)
- Industrial exhaust silencer – 16 dB noise reduction
- Integral fuel tank with 67 L capacity
Documentation:
- User Manual for operation, installation and maintenance
- Wiring Diagram
- Test Report
- Maintenance Schedule
- Catalogues for Engine, Alternator & AVR
Genset Optional Features
- Manual & Automatic Transfer Switches
- Synchronizing & Totalizing Panels
- Fuel water separator
- Water jacket heater
- Oil heater
- Fuel heater
- Battery heater
- Anti-condensation Heater
- Air Shut-off Valve
- Oil Sampler
- Pre-lube Oil Pump