• Mon-Fri 7:30-17:30 I Sat -Sun Closed

Ghaddar Generator CT45 – CT50S (50 Hz) powered by Cummins

Product description

Ratings @ 0.8 PF

Voltage*

230/400 V

Frequency*

50 Hz

Prime rating

CT45*

43 KVA

Stand-by Rating

CT50S*

49 KVA

Ghaddar Generator CT45 – CT50S (50 Hz) powered by Cummins

The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.

Notes

  1. The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
  2. This generating set is of fixed speed of 1500 rpm.
  3. CT45 (prime power): variable load and unlimited hour usage with an average load factor of 80% of the prime rating over each 24-hour period. A 10% overload is permitted for 1 hour in every 12 hours of operation.
  4. CT50 (standby power): variable load limited to an annual usage up to 500 hours, of which 300 hours may be continuous running. No overload is permitted.

Engine Technical Data

Make & ModelCUMMINS 4BTAA3.3-G16
Cylinders & Arrangement4; Vertical in-line
Bore & Stroke (mm)95 × 115
Induction systemTurbo charged & Charge Air Cooled
CombustionDirect injection
Cycle4 stroke
Compression ratio17.5:1
Cooling SystemWater cooled
Displacement3.3 liters
Lube oil capacity7.9 liters Max
Coolant capacity13 liters
Standard governorElectronic
Engine Speed (rpm)1500
Consumption @ 100% Load (L/H) 11
Consumption @ 75% Load (L/H) 8
Consumption @ 50% Load (L/H)6
Consumption @ 25% Load (L/H)3
Radiator Cooling Air Flow (m3/s)1.971
Emissions regulationsFuel Optimized
Exhaust temperature (°C, max)539
Max exhaust gas flow (m3/min)16.2
Max. allowed back pressure (kPa)10.2

The above performance data are valid as per the following specs:

  • Diesel fuel according to BS2869 Class A2 or equivalent.
  • Lubricating oil according to Grade SAE 15W-40 API CI4.
  • Coolant mixture: 50% antifreeze and 50% fresh water.

Alternator Technical Data

Make & ModelLeroy Somer TAL042H
Frequency / No. of poles50Hz / 4P
Ingress protectionIP23
Insulation classH
Terminals (Optional)6 (12)
Excitation systemSHUNT
Winding pitch2/3
AVR modelR150
Overspeed2250 R.P.M.
Voltage regulation±1%
Coolant air flow0.25 m3/s

Certification

  • The complete generating set is type-tested according to ISO 8528-8 standard.

Control Panel Specifications

GMP260MKIII (DSE6110 MKIII) panel is an automatic start genset panel of microprocessor-based design, capable of CAN-bus J1939 interface with electronic engines. Configurable via PC software or fascia buttons.
Optional DSE6120MKIII for mains monitoring. Circuit breaker: Schneider or ABB, 3P MCB (4P optional).

 

Construction

Sheet FabricationCNC shearing & bending
Paint typeHeat-treated powder-coated
Paint applicationElectrostatic corona spraying
Durability tests
  • Impact [EN ISO 6272]
  • Salt spray resistance [ASTM B117-73]
  • Humidity resistance [ASTM D2247]
Compliance
  • Compliant with [ISO8528-8]
  • Clearance & Creepage [IEC60355-1]
  • Leakage current & Dielectric strength [IEC60355-1]
  • Protection against electric shock [IEC600 364-4-41]
Degree of protectionIP55
Wire crimping
  • Crimping force up to 20 kN
  • Accuracy of 0.01 mm
  • Each crimp checked by Komax CFA+
Wire coding
  • Coded by color and cross-section
  • Coded by printed numbers
  • Coded by printed function of the wire

Certification

  • The control panel is certified by an ISO17025 accredited laboratory to have IP55 according to IEC60355.

Genset Standard Features

Assembly: Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528.

Fabrication:

  • Engine/alternator assembly rests on skid with anti-vibration mounting pads.
  • Skid made of durable sheet metals and beams exceeding “Vibration & Torsion” resistance norms.
  • Skid-mounted fuel tank supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
  • Control panel enclosure made of reliable metal sheet.

Paint:

  • Skid and control panel enclosure painted with heat-treated, powder-coated electrostatic corona spraying.
  • Paint durability tested against:
    • Impact (EN ISO 6272)
    • Salt Spray Resistance (ASTM B117-73)
    • Humidity Resistance (ASTM D2247)

Works-Testing:

  • All gensets tested prior to dispatch.
  • Test automatically generated and checked according to ISO8528.
  • Test certificate issued for each genset.

Equipment:

  • Water-cooled radiator with belt-driven blower fan and full guarding
  • Electric starter with solenoid relay
  • Battery charging alternator
  • Electronic governor with Energized-to-run solenoid
  • Replaceable fuel, oil and air filters
  • Heavy-duty lead-acid battery with matching capacity (Amps & CCA)
  • Industrial exhaust silencer – 16 dB noise reduction.
  • Integral Fuel Tank with 117 L capacity

Documentation:

  • User Manual (Operation, Installation, Maintenance)
  • Wiring Diagram
  • Test Report
  • Maintenance Schedule
  • Catalogues for Engine, Alternator & AVR

Genset Optional Features

  • Manual & Automatic Transfer Switches
  • Synchronizing & Totalizing Panels
  • Fuel water separator
  • Water jacket heater
  • Oil heater
  • Fuel heater
  • Battery heater
  • Anti-condensation heater
  • Air Shut-off Valve
  • Oil Sampler
  • Pre-lube Oil Pump

Shipping Dimensions (Open Set):

  • Length: 2500 mm
  • Width: 950 mm
  • Height: 1550 mm
  • Weight: 1100 Kg
wdt_ID Genset Model Cummins Engine Leroy Somer Alternator Phase Frequency (Hz) Voltage (V) Prime Power (KVA) Standby Power (KVA) Download Catalogue View Details
14 CT30-CT33S X3.3-G1 TAL042C 3 50 230/400 32 35
15 CT45-CT50S 4BTAA3.3-G16 TAL042F 3 50 230/400 43 49
16 CT50-CT55S 4BTAA3.3-G15 TAL042H 3 50 230/400 50 55
17 CT60-CT66S 4BTAA3.3-G14 TAL042H 3 50 230/400 60 66
18 CT100-CT110S 6BTA5.9-G5 TAL042D 3 50 230/400 100 110
19 CT135-CT150S 6BTAA5.9-G6 TAL044H 3 50 230/400 135 150
20 CT150-CT165S 6BTAA5.9-G7 TAL044J 3 50 230/400 150 165
21 CT200-CT220S QSB7-G5 TAL044M 3 50 230/400 193 220
22 CT250-CT275S QSL9-G3 TAL046D 3 50 230/400 250 275
23 CT300-CT330S QSL9-G5 TAL046F 3 50 230/400 300 330
24 CT360-CT390S NTA855-G4 TAL046H 3 50 230/400 358 392
25 CT370 – CT410S QSG12-G3 TAL046H 3 50 230/400 370 409
26 CT410-CT450S QSZ13-G7 TAL0473A 3 50 230/400 410 450
27 CT415-CT455S QSG12-G4 TAL0473A 3 50 230/400 416 455
28 CT460-CT530S QSZ13-G5 TAL0473C 3 50 230/400 461 531
29 CT500-CT550S-QSZ QSZ13-G10 TAL0473C 3 50 230/400 520 568
30 CT500-CT550S-KTA KTA19-G4 TAL0473C 3 50 230/400 500 550
31 CT500-CT550S-M15 M15-G8 TAL0473C 3 50 230/400 500 550
32 CT500-CT550S-QSX QSX15-G8 TAL0473C 3 50 230/400 496 553
33 CT640-CT700S VTA28-G5 TAL0473F 3 50 230/400 641 701
34 CT750 – CT825S QSK23-G2 TAL049C 3 50 230/400 750 825
35 CT820-CT900S QSK23-G3 TAL049C 3 50 230/400 801 864
36 CT900-CT1000S KTA38-G3 TAL049E 3 50 230/400 900 1,000
37 CT1000-CT1100S-QST QST30-G4 TAL049E 3 50 230/400 1,000 1,100
38 CT1000-CT1100S-KTA KTA38-G14 TAL049E 3 50 230/400 1,000 1,100
Genset Model Cummins Engine Leroy Somer Alternator Frequency (Hz) Voltage (V) Prime Power (KVA) Standby Power (KVA)